Modbus temperature humidity sensor
The Veswe RS-WS-N01-8-EX is an industrial Modbus Temperature Humidity Sensor featuring an RS485 interface. Housed in a durable ABS plastic enclosure with integrated vents, it includes a rear slot for tool-free DIN rail mounting, ensuring a clean and secure installation in control cabinets.
This smart sensor communicates via the standard Modbus-RTU protocol, offering seamless,integration with major industrial software such as Kingview, 3D Force Control, and MCGS HMI. It is fully compatible with PLCs and custom user-developed platforms, making it a versatile choice for building automation and industrial control systems.
- Model: RS-WS-N01-8-EX
- MOQ: 1 PCS
- Delivery date: within 24 hours
- Inquire About Price Now
Inquiries: Email: contact@veswe.com | WhatsApp: +8613418148929
About - Modbus rtu temperature sensor
Datasheets
- Power supply: 5-30V DC
- Maximum power consumption: 0.1W
- Measure range: -20℃~+60℃, 0%RH~80%RH
- Accuracy: ±3%RH(60%RH,25℃), ±0.5℃(25℃)
- Resolution: 0.1℃, 0.1%RH
- Communication protocol: ModBus-RTU communication protocol
- Output signal: RS485
- Data refresh time: 1s
- Long-term stability: Temperature≤0.1℃/y, Humidity≤1%RH/y
- Response time: Temperature≤25s (1m/s wind speed), Humidity≤8s (1m/s wind speed)
- Parameter setting: via software
Communication protocol - VRS-WS-N01-8-EX
1. Basic communication parameters
| Code | 8 bit binary system |
| Data Bit | 8 bit |
| Odd-even Revi-sion Bit | None |
| Stop Bit | 1bit |
| Incorrect Revis-ion | CRC(Redundant cyclic codes) |
| Baud Rate | 2400bit/s, 4800bit/s, 9600 bit/s options, the factory default 4800bit/s |
2. Data frame format definition
Using Modbus-RTU communication protocol, the format is as follows:
Initial structure ≥4 bytes of time
Address code = 1 byte
Function code = 1 byte
Data area = N bytes
Error check = 16-bit CRC code
Time to end structure ≥ 4 bytes
Address code: the address of the transmitter, which is unique in the communication network (factory default 0x01).
Function code: the function instruction of the command sent by the host, this transmitter only uses the function code 0x03 (read register data).
Data area: The data area is the specific communication data, pay attention to the high byte of the 16bits data first!
CRC code: two-byte check code.
Host query frame structure:
| Address Code | Function Code | Register Origin Address | Register Length | Revision Code in Low Position | Revision Code in High Position |
|---|---|---|---|---|---|
| 1byte | 1byte | 2bytes | 2bytes | 1byte | 1byte |
Slave response frame structure:
| Address Code | Function Code | Effectiveness Byte NO. | Data Area One | Data Area Two | Data Area N | Revision Code |
|---|---|---|---|---|---|---|
| 1byte | 1byte | 1byte | 2bytes | 2bytes | 2bytes | 2bytes |
3. Register address
Register Address | PLC or Configuration Address | Content | Operation |
|---|---|---|---|
| 0000 H | 40001 | Humidity | Read only |
| 0001 H | 40002 | Temperature | Read only |
4. Communication protocol example and explanation
Example: read the temperature and humidity value of device address 0x01
Query frame (hexadecimal):
| Address Code | Function Code | Origin Address | Data Length | Revision Code in Low Position | Revision Code in High Position |
|---|---|---|---|---|---|
| 0x01 | 0x03 | 0x00 0x00 | 0x00 0x02 | 0xC4 | 0x0B |
Response frame (hexadecimal): (For example, the temperature is -10.1℃ and the humidity is 65.8%RH)
| Address Code | Function Code | Return Byte Number | Humidity Number | Temperature Number | Revision Code in Low Position | Revision Code in High Position |
|---|---|---|---|---|---|---|
| 0x01 | 0x03 | 0x04 | 0x02 0x92 | 0xFF 0x9B | 0x5A | 0x3D |
Temperature calculation:
When the temperature is lower than 0 ℃, the temperature data is uploaded in the form of complement code.
Temperature: FF9B H(hex) = -101 => temperature = -10.1℃
Humidity calculation:
Humidity: 292 H (Hex) = 658 => Humidity = 65.8%RH
About - Modbus rtu temperature sensor
Modbus temperature sensor features
1. The sensor adopts an integrated design with a built-in temperature and humidity measuring element, and the overall appearance is small and exquisite, which is suitable for installation in a small place to measure temperature and humidity.
2. The Modbus RTU temperature humidity sensor has pluggable wiring terminals, easy to install, and easy to maintain during use.
3. High-quality measurement unit imported from Switzerland, accurate measurement.
4. 10~30V wide voltage range power supply, complete specifications.
Industry Knowledge
Top 3 Types of Water Quality Parameters | Veswe Water Quality Monitoring Sensors
Contact us
Our colleague: Jack
Phone/ Whatsapp: +86 13418148929
Email: contact@veswe.com
Address:Floors 1–4, No. 269 Nanda Highway, Dashi Street ,Panyu , Guangzhou, Guangdongdong, China